Chapter 5 Installing the Server Into a Rack 5-9
8. Align the server so that the thumbscrews on its sides fit into the slide mounts in
the rack (see
FIGURE 5-8).
If necessary, readjust the slide mounts so that the server aligns correctly. This job is
easier with the thumbscrews done up finger-tight.
FIGURE 5-8 Adjusting the Slide Mounts and Screwing the Server Into the Rack
9. Tighten the slide mounts in the rack.
10. Use a screwdriver to tighten the thumbscrews on the side of the server.
The server is now securely installed in the rack.